Understanding HVAC Lifecycles: When to Repair vs. When to Replace

March 14, 2025

Commercial HVAC systems are a major investment, and building owners often face a critical decision: repair the existing system or invest in a full replacement? While repairs can extend the life of your equipment, there comes a point where replacing the unit is the smarter financial and operational choice. In this post, we’ll break down key factors that determine when to repair and when to replace your HVAC system.

1. The Typical HVAC Lifecycle


Most commercial HVAC systems last 15-25 years, depending on maintenance, usage, and environmental factors. Some of these are driven primarily by Here’s a general breakdown of common equipment lifespans:

System Expected Lifespan
Rooftop Unit (RTU) 15-20 years
Air Handlers 20-30 years
Heat Pumps 15-20 years
Split Systems 15-20 years
Chillers 20-25 years
Cooling Towers 20-30 years
Boilers 20-30 years
Base-Mounted Pumps 20-30 years
Pipe -Mounted Pumps 10-15 years
Terminal Units 20-25 years
Metal Ductwork 40-60 years
Flexible Ductwork 15-30 years

While these are general guidelines, efficiency, maintenance costs, and technological advancements play a role in deciding when to upgrade.


With that being said, systems and components can age differently. We call the two aging mechanisms cycle aging and calendar aging.

Component Primary Aging Mechanism Notes
Compressors Cycle Aging Frequent start-stop cycles, load fluctuations, and refrigerant pressure changes cause wear. Hard starts and short cycling accelerate failure.
Fans & Blowers Cycle Aging Bearings and motors degrade over time due to constant operation, but calendar aging can also occur due to dust accumulation and corrosion.
Coils (Evaporator, Condenser, Heating) Calendar Aging Corrosion, fouling, and refrigerant leaks occur over time, reducing efficiency. Corrosion-resistant coatings can extend lifespan.
Building Automation System (BAS) Controllers Calendar Aging Aging occurs due to outdated software, component degradation, and communication failures.
Cooling Towers Both Fans and pumps experience cycle aging; structural materials (metal, fiberglass), and fill material degrade due to calendar aging from water exposure, scaling, and biological growth.



2. Key Signs It’s Time to Repair

If your HVAC system is experiencing issues but is still within its expected lifespan, repairs may be the best choice. Consider repairing if:

The issue is minor (e.g., a faulty sensor, valve replacement, or refrigerant leak)
Repair costs are less than 30% of the cost of a new system
Your energy bills are stable and reasonable
The unit is under 15 years old
The problem is due to lack of maintenance (e.g., clogged filters, dirty coils)


Example Scenario:
An
8-year-old packaged rooftop unit is struggling due to a failing compressor. If replacing the compressor is significantly cheaper than a new unit, and the system still meets the building’s needs, repairing makes sense.


3. When It’s Time to Replace

Sometimes, repairing is just delaying the inevitable—and costing you more in the long run. You should consider replacing your system if:

🚨 The unit's age is within 80% of its expected lifespan, greater
🚨
Repairs exceed 50% of the replacement cost
🚨
Your energy bills are rising despite no major operational changes
🚨
The system uses outdated refrigerants (like R-22, which is now phased out and can be cost-prohibitive to procure)
🚨
The unit struggles to maintain temperature or humidity levels


Example Scenario:
A
22-year-old chiller has had multiple breakdowns, and a recent failure requires a $30,000 repair. A new, energy-efficient chiller would reduce operating costs significantly and qualify for utility rebates. Replacing the unit is the smarter financial choice.


4. Cost Analysis: Repair vs. Replacement

A good rule of thumb: if the cost of a major repair exceeds 50% of the cost of a new unit, replacement is the better option.

Let’s break down this example of R-22 rooftop unit from the 2000's:


Option Cost Remaining Life Annual Energy Cost Total 5 Year Cost
Repair RTU $12,000 5 years $7,200 $48,000
Replace RTU $20,000 20 years $5,000 $45,000

In this case, the replacement provides a longer service life, better energy efficiency, and pays for itself within five years.


5. Benefits of Upgrading Your HVAC System

If a replacement is needed, the benefits go beyond just avoiding repair costs:

✔️ Lower Energy Bills – Newer units are often 20-40% more efficient, thanks to variable speed fans, compressors, and new refrigerant developments
✔️
Rebates & Incentives – Many utilities offer financial incentives for high-efficiency HVAC upgrades
✔️
Better Indoor Air Quality – Improved filtration and ventilation
✔️
Less Downtime – Fewer emergency repairs and disruptions
✔️
Smart Controls & Automation – Modern units integrate with building automation systems for optimized performance


6. How Verdius Energy Can Help

At Verdius Energy, we specialize in helping building owners navigate HVAC replacement and retrofit decisions with a focus on lifecycle cost, sustainability, and occupant comfort. Our energy audits and compliance services ensure that your building operates efficiently while avoiding costly fines and unnecessary expenses.


Proactive planning for HVAC repairs and replacements helps reduce unexpected costs, improve building performance, and ensure compliance with local energy ordinances. If you’re unsure about your next step, Verdius Energy is here to guide you.

Would you like a consultation? Schedule a call with us today.

March 14, 2025
If you’re looking into an energy audit for your building, one of the first questions you’ll ask is: How much does it cost? The answer varies depending on factors like the building type, size, and complexity of its systems. Most firms in the industry charge a fixed price per square foot , but at Verdius Energy, we take a different approach—one that aligns cost with value rather than an arbitrary formula.
Heat recovery air handler graphic in a BAS system
February 3, 2025
🚀 Orlando property owners, it’s time to take action.
January 9, 2025
There are several ways Atlanta buildings may be exempt from the energy audit mandate. In certain cases, eligible buildings may have their deadlines extended or deferred.
September 5, 2024
These standards are a growing challenge for many organizations
June 11, 2024
Transforming Fresh Air Delivery with Modern Heat Pump Technology
Energy Audits in Atlanta
January 16, 2024
A Guide for Savvy Property Managers & Owners
Ecobee
January 9, 2024
A thermostat setback refers to the intentional adjustment of temperature settings on a thermostat (or group of thermostats, or even a whole building) to a lower or higher level during specific periods when a building or space is unoccupied or when occupants are asleep. The purpose of a setback is to reduce energy consumption by allowing the heating or cooling system to operate less frequently or at a lower capacity when the indoor conditions require less active temperature control. This energy-saving strategy is commonly employed to optimize the balance between comfort and efficiency, ensuring that energy is used only when necessary. Reduced Energy Consumption: The primary advantage of setbacks lie in their ability to curb energy consumption. When a space is unoccupied or when occupants are not actively using a specific area, there is no need for the HVAC system to maintain a constant temperature. By allowing the temperature to fluctuate slightly during these periods, energy consumption is significantly reduced, leading to lower utility bills and decreased overall environmental impact. There are two factors that impact the energy savings harvested from setbacks: The magnitude of the setback - This is how "far" the setback temperature is compared to occupied temperature setpoints. For example, if thermostats maintain the temperature at 72°F normally, a 65°F setback would have a magnitude of 7°F, whereas a 68°F degree setback has a magnitude of 4°F. The duration of the setback - how long the setback is maintained. Is the setback just overnight? Or does it include weekends as well? The duration of setbacks will depend heavily on the occupancy schedule of the building. Generally, energy savings are approximately proportional to the magnitude of the setback and the duration of the setback. Magnitude of setback (°F from normal setpoint) x duration of setback (hours/week) ∝ energy savings Other Benefits: Optimized HVAC Operation: HVAC systems operate most efficiently when they're not constantly cycling on and off. Setbacks enable the HVAC system to work in longer, more stable cycles, avoiding the frequent starts and stops that can contribute to increased wear and tear of motors, compressors, actuators, and valves. This optimized operation not only extends the lifespan of the equipment but also ensures it runs at peak efficiency when needed. Thermal Inertia and Recovery: Buildings possess thermal inertia, meaning they retain heat or coolness even after the HVAC system has been turned off. By strategically implementing setbacks, the indoor temperature is allowed to drift slightly from the desired setpoint. This approach utilizes the thermal inertia of the building, reducing the need for immediate heating or cooling when occupants return, as the space can recover to the desired temperature more efficiently. Zone Control Strategies: Advanced HVAC systems equipped with zone control capabilities can benefit greatly from setbacks. By selectively adjusting temperatures in different zones based on occupancy patterns, setbacks can be tailored to specific areas within a building, ensuring precise climate control where and when it's needed. This level of customization enhances energy efficiency by avoiding unnecessary heating or cooling in unoccupied zones. Even further, occupancy-based control of setpoints and setbacks can use zone-level occupancy sensors to automatically shift between the occupied setpoint and the unoccupied setback temperatures. This has made its way into consumer-grade tech like the Nest and Ecobee thermostats, and is slowly making it's way into commercial building automation systems. Check Your Thermostats: Take a moment to do this. Do they have a schedule or setback that aligns with occupancy? If not, it may be something to do right now that could save you hundreds or even thousands of dollars with little to no comfort impact. If you have a reason on the books for not using setbacks, it may be time to revisit that justification. ASHRAE 90.1-2019 recommends a heating setback of 10°F below the occupied heating setpoint, and a cooling setback of 5°F above the occupied cooling setpoint. You do not have to start with that! Try 2°F, or even 1°F at first, see how it goes, and increment from there. Want to go beyond setbacks and save even more energy? Get in touch with Verdius Energy today to learn about all the services we offer. Conclusion: The merits of heating and cooling setbacks are rooted in their ability to optimize energy consumption, improve HVAC system efficiency, leverage thermal inertia, and enable advanced zone control strategies. By incorporating setbacks into your HVAC controls, you not only contribute to a more sustainable, energy-efficient future, but also enjoy the tangible benefits of reduced energy bills, and prolonged equipment lifespan.
December 28, 2022
Modern apartments still suffer from freeze risks, especially in sunbelt climates like Atlanta were deep freezes are uncommon
Benchmarking City of Atlanta
July 13, 2022
The City of Atlanta passed a Building Benchmarking and Energy Audit Ordinance on May 30, 2017. 
Show More